1. Product overview
The CG6900 series employs a full-color TFT-LCD screen as the human-machine interface (HMI), significantly enhancing interactive capabilities. It enables digital, visual, and intelligent management of switchgear operational status, serving as a critical terminal device for smart power distribution networks.
2. Functions & features
·Panoramic status display and precise monitoring
Panoramic status display: circuit mimic diagram, switch status indication, circuit breaker position indication, grounding switch position indication, spring charge state indication, HV live-line indication and interlock, and intelligent temperature control etc.
Adjustable functions: The above functions can be freely combined according to user needs to meet different usage requirements.
Precision monitoring: The digital temperature and humidity control makes the temperature more accurate and more universal, and the advanced disconnection alarm circuit is used to avoid false alarms or missed alarms.
·Human-Machine interface
Full-color LCD display enables cost-effective mimic diagram updates with high-density information visualization and intuitive user operation.
· Remote monitoring
RS485 interface: Adjustable baud rate (4800/9600), MODBUS protocol
3. Technical specifications
Display: Primary mimic diagram, switch status, T/H values, HV interlock, and heating/ventilation/fault alarms
● Status signal input: dry contact inputs (closed-circuit active)
● HV live indication: striking voltage indication/lockout threshold voltage: compliance with GB 25081-2010
● Range and precision of temperature measurement: -20~80℃ ±1% FS
● Range and precision of humidity measurement: 20%~98%RH ±5%RH
● Heater activation conditions (if any one of them is met, heating will be started)
1. Cabinet temperature < heater setpoint
2. Cabinet humidity > heater setpoint
3. Manual override
● Heater deactivation conditions (heating stops only when all three conditions below are simultaneously met)
1. Cabinet temperature > heater setpoint +5°C
2. Cabinet humidity < heater setpoint -10% RH
3. Manual override reset
● High-temperature ventilation activation conditions:
1. Cabinet temperature > fan setpoint
2. Manual override
● High-temperature ventilation deactivation conditions:
1. Cabinet temperature < fan setpoint -5°C
2. Manual override reset
● Heater relay (with wire-break alarm) contact power: 2 x 220VAC/3A
● Over-temperature ventilation output relay: 220V AC/3A (Single NO dry contact).
● High-voltage live indicator interlock output relay: 220V AC/3A (Single NO dry contact).
● Alarm output relay: 220V AC/3A (Single NO dry contact; contact closes upon any of the following conditions).
1. Heater disconnection alarm
2. Sensor failure alarm
3. Over temperature alarm
● RS485 interface: Adjustable baud rate (4800/9600), MODBUS protocol
● Instrument power supply and power consumption: AC/DC 90~260V, power consumption <15W
● Anti-interference characteristics (electromagnetic compatibility and electrical strength)
EFT (Fast Transient): GB/T17626.4-2008 Level Ⅲ
ESD (Electrostatic Discharge): GB/T17626.2-2006 Level Ⅲ
Voltage dips, short interruptions, and voltage variations: GB/TD626.11-2008 Level Ⅲ
Surge Immunity: GB/T17626.5-2008 Level Ⅲ
● Panel Cutout: 207mm*127mm(CG6900A model)
Working environment: temperature: -20~50℃, humidity: <90%RH
4. Applications
Substations: Real-time monitoring of switchgear status to prevent trip accidents caused by misoperation.
Distribution Rooms: Ensures safe operation of low-voltage (LV) distribution equipment and reduces failure risks.
Industrial Power: Monitors electrical equipment in factories, mines, and similar facilities to enhance production efficiency.
Renewable Energy: Delivers switchgear status monitoring solutions for photovoltaic (PV), wind power, and other renewable energy generation systems.