1. Product overview
KW2000 Electric Energy and Power Quality Intelligent Detector is an intelligent device that integrates electric energy metering and power quality monitoring. It is designed to provide real-time monitoring and analysis services for the use and quality of electric energy in the power system. By precise data collection and intelligent diagnosis, it helps users optimize the energy efficiency, and improve the stability and reliability of the power system.
2. Functions & features
· Comprehensive power quality monitoring
Fundamental electrical parameters: effective value of voltage/current, power (active/reactive/apparent), power factor, frequency.
Power quality metrics: Measurement of voltage and current harmonic content and total harmonic distortion up to 31 times
Monitoring of voltage and current imbalance.
Energy efficiency analysis: Time-of-use energy metering, demand monitoring, and loss calculation.
· Smart Analysis & Optimization Management
Built-in intelligent algorithms automatically analyze trends in electricity usage, identify abnormal states, and issue warnings.
It supports energy efficiency evaluation, helps users optimize their electricity consumption strategies, and reduces energy consumption costs.
It provides historical data storage and analysis functions to help users optimize their energy management strategies.
It supports the generation of energy usage curves and reports to provide data support for decision-making.
· Convenient and efficient remote monitoring
It supports Modbus RTU protocol with optoelectronic isolated RS-485 communication interface for remote data monitoring and management.
· Easy installation and strong compatibility
Modular design, simple and fast installation process, no need for large-scale modification of existing equipment.
Compatible with multiple types of power systems, with a wide range of applications.
3. Technical specifications
Main technical parameters of the instrument
Measurement parameters | Measurement range | Measurement error | Resolution | Overload |
Voltage | 10.0~350V AC | ±(0.5% reading +0.01V) | 0.01V | 120% |
Current | 0.02~5A AC | ±(0.5% reading +0.001A) | 0.001A | 120% |
Active power | U*I*COSΦ | PF=1.0: ±(0.5% reading +0.1W) | 0.1W | |
Active energy | 400000000 KWh | 0.1Wh | ||
Reactive power | U*I*SINΦ | PF=0.0: ±(0.5% reading +0.2Var) | 0.1Var | |
Reactive energy | 400000000 KVarh | 0.1Varh | ||
Power factor | -1.00~1.00 | ±(0.5% reading +0.001) | 0.001 | |
Frequency | 45~65Hz | ±0.01Hz | 0.01Hz | |
Harmonic | 1- 31 times | Class B(GB/T 19862-2005) | ||
Phase angle | 0~360 deg | ±(0.5% reading +0.1deg) | 0.1deg | |
Imbalance | 0~1 | ±(0.5% reading +0.001) | 0.001 | |
Voltage and frequency deviation | -1~1 | ±(0.5% reading +0.001) | 0.001 |
Other technical parameters
Voltage input (per line) | |
Input range | 5~400V |
Input impedance | 1.2MΩ |
Current input (per line) | |
Input range | 0.05~5A |
Input impedance | <0.1Ω |
Serial port | |
Type | Optoelectronic isolation RS-485 |
Protocol | Modbus-RTU |
Baud rate | 4800、9600、19200、38400 |
Operating environment | |
Temperature | -20~55℃ |
Humidity | <75%RH |
Atmospheric pressure | 80~106 |
Working power supply | |
Supply voltage | 85~265VAC 100~300VDC |
Power supply frequency | 45~65Hz or direct current |
Overall Power Consumption (with extension) | <4VA |
Dimension | 75 mm × 110 mm × 106 mm |
4. Applications
Industrial electricity: Real-time monitoring of electricity usage, optimization of production electricity efficiency, and reduction of energy consumption costs.
Commercial electricity: Ensure the power quality of commercial premises and improve the stability of equipment operation.
Renewable energy systems: It provides power quality monitoring solutions for new energy generation systems such as photovoltaics and wind power.
Public facilities: Suitable for energy management in public places such as hospitals, schools, airports, etc., to enhance electricity safety.