1. Key models
CG208E-RS, CG217EF-TH, CG227E-PQ, CG237E and CG239E etc.
2. Product overview
The CG200 series digitally displays the temperature, humidity value and temperature and humidity control range inside the power equipment cabinet, and monitors the high temperature, low temperature and over-humidity status inside the cabinet in real time. The heater or exhaust fan switch is automatically controlled according to the on-site conditions. Multiple protection measures effectively prevent component failure caused by excessively high or low temperature in the cabinet or accidents such as creepage and flashover caused by excessive humidity with the features of small start-up control point error, timely and accurate fan action, high stability and high reliability.
3. Functions & features
·User-friendly design, intuitive visibility & effortless operation
LED digital display, intuitively visible parameters, membrane button operation, supporting remote RS485 communication.
·Precise monitoring and intelligent control
High-precision sensing: temperature accuracy: ±1°C (-20°C ~ +100°C); Humidity accuracy: ±3%RH (20%RH to 99%RH)
Intelligent control mode: multiple outputs simultaneously and automatically control heating, dehumidification and other equipment, supporting both manual and automatic control modes.
Adjustable parameters: users can set the upper and lower limits of temperature and humidity according to their needs, and the controller will automatically adjust according to the set value.
Support remote RS485 communication
·Safety and protection
Flame-retardant enclosure: V0 rated
Triple-protection design: fungus proof, moisture resistant & salt spray protected
Alarm system: threshold alert & real-time anomaly warning
·Simplified installation
Support panel and DIN- rail installation, adaptable to different cabinet structures.
-Energy saving and environmental protection
It adopts low power consumption design, energy saving and environmental protection, and long-term use can effectively reduce energy consumption.
4. Technical specifications
- Temperature specifications: -20℃~100℃,±1℃
- Humidity specifications: 20%RH~99%RH,±3%RH
·Support connection of 1-2 heaters or exhaust fans, with the heating and exhausting be automatically started and stopped according to temperature and humidity settings
· Heaters or fans operation faults can be detected, and the alarm signals can be output automatically in case of failures.
·Alarm signals can be provided for over-temperature, over-humidity, low temperature, low humidity, etc., and various customizations can be made according to customer requirements
· Operating environment: Temperature: -10~50℃, humidity: <95%RH
· Power supply: AC220V/50HZ, power consumption: ≤10VA
· Dimensions & cutout dimensions: For multiple dimensions & cutout sizes available, see Product Selection Guide
5. Applications
Electrical equipment: high-voltage switchgears, ring main units, compact substations, and terminal/junction boxes etc.
Industrial Environments: automated production lines,instrumentation control cabinets, underground substations.
Critical Infrastructure: data center racks, telecom base stations, rail transit equipment cabins.