1. Product overview
The CG2000E is specifically designed for the comprehensive collection of electrical parameters in 50/60Hz power supply systems. It can measure and display three-phase current, three-phase voltage, active power, and electrical energy (kWh). (The electrical energy values are solely for internal secondary metering, assessment, and accounting within the enterprise and are not to be used for pricing, measurement, or payment purposes.)
2. Functions & features
· Multi-function integrated
Integrating ammeter, voltmeter, wattmeter, and energy meter into one unit
It features intelligent integrated circuit design with the function of True Root Mean Square (Trms) measurement for voltage and current, ensuring accurate measurement and display even when voltage and current waveforms are distorted.
By setting the CT ratio on the panel, the primary operating current of the power distribution system can be displayed intuitively, which is suitable for power distribution systems with three-phase three-wire connection or three-phase four-wire connection.
· Smart interconnection
Full digital display
RS485 serial interface, ModBus protocol, selectable communication baud rate: 4800 or 9600.
3. Technical specifications
① Wiring method
3P3 (three-phase three-wire) or 3P4 (three-phase four-wire)
② Signal input
Current: rated input current AC: 1A, 5A
Voltage: rated input voltage AC: 100V, 220V, 380V
Three-phase three-wire system (3P3W): when using a 2-CT input configuration, only Phase A and Phase C currents are required, while Phase B remains unconnected.
Allowable overrange: instantaneous: current 10 times/5 seconds, voltage 2 times/1 second
Continuous: 1. 2x
③ Serial communication
RS485 serial interface, ModBus protocol, selectable communication baud rate: 4800 or 9600.
④ Power measurement range and accuracy
Current: 0~5A or 0~1A with an accuracy of Class 0.5
Voltage: 0~450V with an accuracy of Class 0.5
Active power: 0~999999.999 Kw with an accuracy of Class 1.0
Active electric energy (accumulated and displayed in kWh): 0~9999999.99 Kwh with an accuracy of Class 1.0
⑤ Anti-interference performance (Electromagnetic compatibility):
EFT (Fast Transient): GB/T17626.4-1999 Level Ⅲ
ESD (Electrostatic Discharge): GB/T17626.2-1998 Level Ⅲ
Voltage dips, short interruptions, and voltage variations: GB/TD626.11-1999 Level Ⅲ
Surge Immunity: GB/T17626.5-1999 Level Ⅲ
⑥ Insulating strength: IEC 60255-5 2KVrms-1min
⑦ Environmental tolerance: operating: IEC 60068-1 & 2, 0°C to +55°C
Storage: IEC 60068-1 & 2, -25°C to +70°C
Damp heat: IEC 60068-1-3, 93% RH at 40°C
⑧ Application environment: free of corrosive gases and metal dust with the altitude < 3000 m
⑨ Working power supply and power consumption: AC or DC 85~265V8VA
4. Applications
Industrial applications: factory power distribution monitoring, motor energy efficiency management
Commercial building applications: power consumption analysis of central air-conditioning systems in shopping malls and hospitals.
Renewable resource: PV plants & EV chargers power metering
Public infrastructure: metro & airport power safety monitoring